Mode | TH-1P- | TH-2P- | TH-3P- | TH-4P- |
Inter Dim.W×H×D(cm) | 40×50×40 | 45×60×45 | 50×75×60 | 100×100×80 |
External Dim.W×H×D(cm) | 92×130×70 | 97×140×75 | 102×155×90 | 152×180×110 |
Temp. Range | -70℃~100℃(+150℃)(A:0℃ B:-20℃ C:-40℃ D:-60℃ E:-70℃ |
*RelativeHumildity Range | 20%~98%R.H. |
Features | Temp. & huml.constancy | ±0.3℃;±2.5%℃ |
Temp. & humi. uniformity | ±0.5℃; ±4%R.H. |
Indication resolution | 0.1℃;0.1%R.H./0.01℃;0.1%R.H. |
Heat-up time (min.) | About 30 to 50 |
Pull-down time (min.) | About 45 to 120 |
Material | Exterior | SUS#304 stainless steel plate |
Interior | SUS#304 stainless steel plate |
Insulation | PU & Fiberglass wool |
Systems | Circulation | Siroco fan |
Heating | SUS#304 stainless steel high-speed heater |
Humidifying | Surface evaporating system |
Cooling | Airtight compressor+evaporator fins+air-cooling condenser |
Dehumidifying | ADP Critical dewpoint cooling/dehumidifying method |
Control | Digital electronic indicators, programmable computer controller+S.S.R. |
Other components | Vacuum glass inspection window, cable p:ort(Φ35mm),control status indicator lights, chamber lamp, experiment separation shelves (freely adjustable 2 pcs). |
Savety devices | Overheating prevention circuit-breaker,compressor overload protection, control system overload prevention, humidifying system overheating and drying out prevention, breakdown indicator light. |
Power source | AC 1Φ/3Φ,220V±10%,50/60HZ. |